B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 331 H2 Multi-Function Digital Output Settings H2- Setting Function Description Control Mode Pg. V/f O LV P M 1B Baseblock 2 Open: Drive is in base block condition. Output is disabled. O O O — 1C Motor 2 Selection Closed: Motor 2 is selected by a digital input (H1- = 16) O O − — 1E Restart Enabled Closed: An automatic restart is performed O O O — 1F Overload Alarm OL1 Closed: OL1 is at 90% of its trip point or greater. O O O — 20 OH Pre alarm Closed: Heatsink temperature exceeds the parameter L8-02 value. O O O — 22 Mechanical Weakening (N.O.) Closed: Mechanical Weakening detected.
O O O — 30 During Torque Limit Closed: When the torque limit has been reached. − O − — 37 During Frequency Output Closed: Frequency is output Open: Operation stopped, Baseblock, DC Injection Braking, or Initial Excitation is being performed. O O O — 38 Drive Enable Closed: Multi-function input closes (H1- = 6A) O O O — 39 Watt Hour Pulse Output Output units are determined by H2-06, outputs 200 ms pulse for each incremented kWh count. O O O — 3C Drive Mode Closed: Local Open: Remote (this signal combines setting values 9 and A). O O O — 3D Speed Search Closed: Speed search is being executed. O O O — 3E PID Feedback Loss Closed: PID Feedback Loss.
PID feedback value is below the level set to b5-13 for longer than the time set in b5-14. O O O — 3F PID Feedback Fault Closed: PID Feedback Fault.PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37. O O O — 4A KEB Operation Closed: KEB is being performed. O O O — 4B Short-Circuit Brake Closed: Short-Circuit Braking is active. − − O — 4C During Fast-stop Closed: Fast-stop command is entered O O O — 4D OH Pre-alarm Time Limit Closed: OH Pre-alarm time limit is passed. O O O — 100 to 14D H2 Parameter Functions Reversed Output Switching of 0 to 92 Reverse the output switching of the multi-function output functions.
Set the last two digits of 1 to reverse the output signal of that specific function.Examples: Setting “108” reverses the output of “During baseblock,” which is setting value 08. Setting “14A” reverses the output of “During KEB operation”, which is setting “4A”. O O O —