B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 343 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L5-02 Auto Restart Operation Selection Sets fault contact activation during automatic restart attempts. 0: Fault output (H2- = E) not active. 1: Fault output (H2- = E) active during restart attempt. 0,1 0 A A A 49F — L5-04 Fault Reset Interval Time Sets the amount of time to wait between performing fault restarts. Enabled when L5-05 is set to 1. 0.5 to 600.0 s 10.0 s A A A 46C — L5-05 Fault Reset Operation Selection Selects the method of incrementing the restart counter. 0:
Continuously attempt to restart and increment counter after successful restart (like Varispeed VS616-F7/G7) 1: Attempt to restart with the interval time set in L5-04. Every trial increments the counter. (like Varispeed VS606-V7) 0 to 1 0 A A A 467 —