B.2 Parameter Table 342 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L3-25 Load Inertia Ratio Sets the ratio between the motor and machine inertia. 0.0 to 1000.0 1.0 A A A 46F — L4: Frequency Detection Use L4 parameters to configure frequency detection operation. L4-01 Speed Agreement Detection Level These parameters configure the multi-function output (H2- = 2, 3, 4, 5) settings "Fref/Fout Agree 1", "Fref/Set Agree 1", "Frequency Detection 1," and "Frequency detection 2". Parameter L4-01 sets the level while parameter L4-02 sets the hysteresis for the Speed Detection Output Function.
0.0 to 400.0 0.0 Hz A A A 499 — L4-02 Speed Agreement Detection Width 0.0 to 20.0 2.0 Hz A A A 49A — L4-03 Speed Agreement Detection Level (+/-) These parameters configure the Multi-Function Output (H2- = 13, 14, 15, 16) settings "Fref/Fout Agree 2", "Fref/Set Agree 2", "Frequency Detection 3," or "Frequency Detection 4". Parameter L4-03 sets the level while parameter L4-04 sets the hysteresis for the Speed Detection Output Function. -400.0 to +400.0 0.0 Hz A A A 49B — L4-04 Speed Agreement Detection Width (+/-) 0.0 to 20.0 2.0 Hz A A A 49C — L4-05 Frequency Reference Loss Detection Selection Sets operation when the frequency reference is lost (reference drops 90% or more within 400 ms).
0: Stop - Drive will stop. 1: Run at L4-06 PrevRef - Drive will run at the percentage set in L4-06 of the frequency reference before loss. 0,1 0 A A A 49D — L4-06 Frequency Reference at Reference Loss Sets the frequency reference when a reference loss was detected and L4-05 = 1. Reference will be: Fref = Fref at time of loss x L4-06. 0.0 to 100.0 80.0 % A A A 4C2 — L4-07 Frequency Detection Conditions 0: No detection during baseblock. 1: Detection always enabled. 0 to 1 0 A A A 470H — L5: Fault Reset Use L5 parameters to configure Automatic Restart after fault.
L5-01 Number of Auto Restart Attempts Sets the counter for the number of times the drive attempts to restart when the following faults occur: GF, LF, OC, OV, PF, PUF, RH, RR, OL1, OL2, OL3, OL4, UV1. If the drive faults after an auto restart attempt, the counter is incremented. When the drive operates without fault for 10 minutes, the counter will be reset. 0 to 10 0 A A A 49E —