omron — L: Protection Function

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 341 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L3-11 OV Suppression Function Selection Enables or disables OV suppression function, which allows the drive to change the output frequency as the load changes, thus preventing an OV fault. 0: Disabled 1: Enabled Note: The frequency reference and motor speed diverge as the regenerative energy begins to flow back into the DC bus and triggers the OV suppression function. Disable this function when using a braking resistor.

0, 1 0 A A - 4C7 — L3-17 Overvoltage Suppression and Stall Prevention Desired DC Bus Voltage Sets the desired value for the DC bus voltage during overvoltage suppression and stall prevention during deceleration. Enabled only when L3-04 = 2 or L3-11 = 1. 150 to 400 V 370 V A A A 462 — L3-20 Main Power Circuit Voltage Adjustment Gain Sets the proportional gain used by KEB, Stall prevention and overvoltage suppression. If OV or UV1 occurs at the beginning of KEB deceleration, slowly increase this setting by 0.1.

0.00 to 5.00 1.00 A A A 465 — L3-21 Accel/Decel Rate Calculation Gain Sets the proportional gain used to calculate the deceleration rate during KEB, OV suppression function and stall prevention during deceleration (L3-04 = 2). This parameter does not typically require adjustment. Increase the value in steps of 1.0 if overcurrent and overvoltage occur. 0.00 to 200.00 1.00 A A A 466 — L3-22 Deceleration Time at Stall Prevention during Acceleration Sets the deceleration time used for stall prevention during acceleration in Open Loop Vector control for PM motors. When set to 0, the drive decelerates at the normal deceleration time.

0.0 to 6000.0 0.0 s − − A 4F9 — L3-23 Automatic Reduction Selection for Stall Prevention during Run 0: Sets the stall prevention level throughout the entire frequency range to the value in parameter L3-06. 1: Automatically lowers the stall prevention level in the constant output range. The lower limit value is 40% of L3-06. 0, 1 0 A A Α 4FD — L3-24 Motor Acceleration Time for Inertia Calculations Sets the time needed to accelerate the uncoupled motor at rated torque from stop to the maximum frequency. Setting the drive capacity to parameter o2-04 or changing E2-11 will automatically set this parameter for a 4-pole motor. 0.001 to 10.000 A A A 46E —