omron — L: Protection Function

B.2 Parameter Table 340 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L3-04 Stall Prevention Selection during Deceleration When using a braking resistor, use setting "0". Setting "3" is used in specific applications. 0: Disabled - The drive decelerates at the active deceleration rate. If the load is too large or the deceleration time is too short, an OV fault may occur. 1: General Purpose - The drive decelerates at the active deceleration rate, but if the main circuit DC bus voltage reaches the stall prevention level (380/760 VDC), deceleration will stop.

Deceleration will continue once the DC bus level drops below the stall prevention level. 2: Intelligent - The active deceleration rate is ignored and the drive decelerates as fast as possible without hitting OV fault level. Range: C1-02 / 10. 3: Stall Prevention with Braking Resistor - Stall prevention during deceleration is enabled in coordination with dynamic braking. 4: Overexcitation Deceleration - Decelerates with the flux level determined by n3-13 (Overexcitation Gain). 0 to 4 1 S S S 492 340 L3-05 Stall Prevention Selection during Run Selects the stall prevention method to use to prevent drive faults during run. 0: Disabled - Drive runs a set frequency.

A heavy load may cause the drive to trip on an OC or OL fault. 1: Decel Time 1 - The drive will decelerate at Decel Time 1 (C1-02) if the output current exceeds the level set by L3-06. Once the current level drops below the L3-06 level, the drive will accelerate back to its frequency reference at the active acceleration rate. 2: Decel Time 2 - Same as setting 1 except the drive decelerates at Decel Time 2 (C1-04). When output frequency is 6 Hz or less, stall prevention during run is disabled regardless of the setting in L3-05. 0 to 2 1 A − A 493 — L3-06 Stall Prevention Level during Run Enabled when L3-05 is set to "1" or "2".

100% is equal to the drive rated current.Decrease the set value if stalling or excessive current occurs with the default settings. 30 to 200 A − A 494 —