omron — L: Protection Function

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 339 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L3: Stall Prevention Function Use L3 parameters to configure the stall prevention function. L3-01 Stall Prevention Selection during Acceleration Selects the stall prevention method used to prevent excessive current during acceleration. 0: Disabled - Motor accelerates at active acceleration rate. The motor may stall if load is too heavy or accel time is too short. 1: General Purpose - When output current exceeds L3-02 level, acceleration stops. Acceleration will continue when the output current level falls below the L3-02 level. 2:

Intelligent - The active acceleration rate is ignored. Acceleration is completed in the shortest amount of time without exceeding the current value set in L3-02. 0 to 2 1 A A A 48F — L3-02 Stall Prevention Level during Acceleration Used when L3-01 = 1 or 2. 100% is equal to the drive rated current. Decrease the set value if stalling or excessive current occurs with default setting. 0 to 150 A A A 490 — L3-03 Stall Prevention Limit during Acceleration Sets stall prevention lower limit during acceleration when operating in the constant power range. Set as a percentage of the drive's rated current. 0 to 100 50% A A A 491 —