B.2 Parameter Table 338 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L2: Momentary Power Loss Use L2 parameters to configure drive functions for momentary power loss conditions. L2-01 Momentary Power Loss Operation Selection Enables and disables the momentary power loss function. 0: Disabled - Drive trips on (UV1) fault when power is lost. 1: Power Loss Ride-Thru Time - Drive will restart if power returns within the time set in L2-02. 2: CPU Power Active - Drive will restart if power returns as long as the CPU is working.
0 to 2 0 A A A 485 — For a restart to occur, the run command must be maintained throughout the ride-thru period. L2-02 Momentary Power Loss Ride-Thru Time Sets the Power Loss Ride-Thru time. Only effective when L2-01 = 1. 0.0 to 25.5 A A A 486 — L2-03 Momentary Power Loss Minimum Baseblock Time Sets the minimum wait time for residual motor voltage decay before the drive output reenergizes after power loss ride-thru. If L2-03 is greater than L2-02, operation resumes after the time set in L2-03. 0.1 to 5.0 A A A 487 — L2-04 Momentary Power Loss Voltage Recovery Ramp Time Sets the time for the output voltage to return to the preset V/f pattern during speed search.
0.0 to 5.0 A A A 488 — L2-05 Undervoltage Detection Level (UV) Sets the DC Bus undervoltage trip level. If this is set lower than the default setting, additional AC input impedance or DC bus reactance may be necessary. Consult with the manufacturer before changing this parameter setting. This value is used for KEB activation if L2-01 > 0. 150 to 210 A A A 489 — L2-06 KEB Deceleration Time Sets the time required to decelerate from the speed when KEB was activated to zero speed. 0.0 to 200.0 0.0 s A A A 48A — L2-07 KEB Acceleration Time Set the time to accelerate to the set speed after recovery from a momentary power loss. If set to 0.0, the active acceleration time is used.
0.0 to 25.5 0.0 s A A A 48B — L2-08 KEB Start Output Frequency Reduction Sets the percentage of output frequency reduction at the beginning of deceleration when a KEB command is input from multi-function input. Reduction = (slip frequency before KEB) x L2- 08 x 2 0 to 300 100% A A A 48C — L2-11 Desired DC Bus Voltage during KEB Sets the desired value of the DC bus voltage during KEB. 150 to 400 V E1- 01 x 1.22 A A A 461 —