omron — L: Protection Function

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 337 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L1: Motor Protection Functions Use L1 parameters to configure motor protective functions. L1-01 Motor Overload Protection Selection Sets the motor thermal overload protection (OL1) based on the cooling capacity of the motor. 0: Disabled 1: Standard Fan Cooled ( 0 to 4 1 S S S 480 382 L1-02 Motor Overload Protection Time Sets the motor thermal overload protection (OL1) time. A larger L1-02 time will increase the time for an OL1 fault to occur. This parameter does not typically require adjustment.

Should be set in accordance with the overload tolerance of the motor. 0.1 to 5.0 1.0 min A A A 481 — L1-03 Motor Overheat Alarm Operation Selection (PTC input) Sets operation when the motor temperature analog input (H3-02/10 = E) exceeds the OH3 alarm level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop using C1-09 3: Alarm Only (“oH3” will flash) 0 to 3 3 A A A 482 — L1-04 Motor Overheat Fault Operation Selection (PTC input) Sets stopping method when the motor temperature analog input (H3-02/10 = E) exceeds the OH4 fault level. 0: Ramp to Stop 1: Coast to Stop 2:

Fast-stop 0 to 2 1 A A A 483 — L1-05 Motor Temperature Input Filter Time (PTC input) This parameter adjusts the filter on the motor temperature analog input (H3-02 or H3-10 = E). Increase to add stability, decrease to improve response. 0.00 to 10.00 0.20 s A A A 484 — L1-13 Continuous Electrothermal Operation Selection Determines whether or not to hold the electrothermal value when the power supply is interrupted. 0: Disabled 1: Enabled 0 to 1 1 A A A 46D —