B.2 Parameter Table Parameter can be changed during run. If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands. The availability of certain functions depends on the control method used. Note: Cycle power to the drive to enable MEMOBUS/Modbus settings. ◆ L: Protection Function L parameters provide protection to the drive and motor, such as: control during momentary power loss, stall prevention, frequency detection, fault restarts, overtorque detection, torque limits and other types of hardware protection. 336 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg.
V/f O LV P M H6-05 Pulse Train Input Filter Time Sets the pulse train input filter time constant. 0.00 to 2.00 0.10 s A A A 430 — H6-06 Pulse Train Monitor Terminal MP Selection Select the pulse train monitor output function (value of the - part of U-). Refer to U: Monitors on page 360 for the list of U monitors. Example: To select U5-01, set “501.” When not using this parameter or when using in the through mode, set “000”. 000, 031, 101, 102, 105, 116, 501, 502 102 A A A 431 — H6-07 Pulse Train Monitor Scaling Sets the pulse output frequency in Hz when the monitor value is 100%. Set H6-06 to “2” and H6-07 to “0”, to make the pulse train monitor output equal to the output frequency.
0 to 32000 1440 Hz A A A 432 —