omron — H Parameters: Multi-Function Terminals

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 335 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M H5-09 CE Detection Time Sets the time required to detect a communications error. Adjustment may be need when networking several drives. 0.0 to 10.0 s 2.0 s A A A 435 — H5-10 Unit Selection for MEMOBUS/Modbus Register 0025H Selects the units used for MEMOBUS/Modbus register 0025H (Output Voltage Reference Monitor). 0: 0.1 V units 1: 1 V units 0, 1 0 A A A 436 — H5-11 Communications ENTER Function Selection Select the function for the enter command that saves parameter data to the drive. 0:

Parameter changes are activated when ENTER command is entered. 1: Parameter changes are activated immediately without ENTER command (compatible with Varispeed VS606-V7). 0, 1 1 A A A 43C — H5-12 Run Command Method Selection 0: FWD/STOP, REV/STOP Method 1: RUN/STOP, FWD/REV Method 0, 1 0 A A A 43D — H6: Pulse Train Input/Output Use H6 parameters to configure Pulse Train I/O operation. H6-01 Pulse Train Input Terminal RP Function Selection Selects pulse train input function. 0: Frequency reference 1: PID feedback value 2: PID setpoint value 3:

Simple PG V/f control mode (can be set only when using motor 1 in the V/f control mode) 0 to 3 0 A A A 42C — H6-02 Pulse Train Input Scaling Sets the number of pulses (Hz) that is equal to 100% of the value selected in H6-01. 1000 to 32000 1440 Hz A A A 42D — H6-03 Pulse Train Input Gain Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is input. 0.0 to 1000.0 100.0 % A A A 42E — H6-04 Pulse Train Input Bias Sets the level of the value selected in H6-01 when 0 Hz is input. -100.0 to +100.0 0.0% A A A 42F —