B.2 Parameter Table 334 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M H4-03 Multi-Function Analog Output Terminal AM Gain Sets terminal AM output level when selected monitor is at 0%. -999.9 to 999.9 0.0% A A A 41F — H5: MEMOBUS/Modbus Communications Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network. H5-01 Drive Node Address Selects drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S-. Cycle power for the setting to take effect. 0 to 20 H 1F A A A 425 — H5-02 Communication Speed Selection Selects the baud rate for MEMOBUS/Modbus terminals R+, R-, S+ and S-.
Cycle power for the setting to take effect. 0: 1200 bps 1: 2400 bps 2: 4800 bps 3: 9600 bps 4: 19200 bps 5: 38400 bps 6: 57600 bps 7: 76800 bps 8: 115200 bps 0 to 8 3 A A A 426 — H5-03 Communication Parity Selection Selects the communication parity for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0: No parity 1: Even parity 2: Odd parity 0 to 2 0 A A A 427 — H5-04 Stopping Method After Communication Error Selects the stopping method when a communication time-out fault (CE) is detected. 0: Ramp to stop 1: Coast to stop 2: Fast-stop 3:
Alarm only 0 to 3 3 A A A 428 — H5-05 Communication Fault Detection Selection Enables or disables the communications time- out fault (CE) detection. 0: Disabled 1: Enabled - If communication is lost for more than two seconds, a CE fault will occur. 0,1 1 A A A 429 — H5-06 Drive Transmit Wait Time Set the wait time between receiving and sending data. 5 to 65 5 ms A A A 42A — H5-07 RTS Control Selection Selects "request to send" (RTS) control: 0: Disabled - RTS is always on. 1: Enabled - RTS turns on only when sending. 0,1 1 A A A 42B —