omron — L: Protection Function

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 345 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L6-04 Torque Detection Selection 2 Sets the response to an overtorque/undertorque condition. overtorque and undertorque are determined by the settings in parameters L6-05 and L6-06. The multi-function output settings (H2-†† = 18 and 19). 0: Disabled 1: OL4 at Speed Agree - Alarm (overtorque Detection only active during Speed Agree and Operation continues after detection). 2: OL4 at RUN - Alarm (overtorque Detection is always active and operation continues after detection). 3:

OL4 at Speed Agree - Fault (overtorque Detection only active during Speed Agree and drive output will shut down on an OL4 fault). 4: OL4 at RUN - Fault (overtorque Detection is always active and drive output will shut down on an OL4 fault). 5: UL4 at Speed Agree - Alarm (undertorque Detection is only active during Speed Agree and operation continues after detection). 6: UL4 at RUN - Alarm (undertorque Detection is always active and operation continues after detection). 7: UL4 at Speed Agree - Fault (undertorque Detection only active during Speed Agree and drive output will shut down on an OL4 fault). 8:

UL4 at RUN - Fault (undertorque Detection is always active and drive output will shut down on an OL4 fault). 0 to 8 0 A A A 4A4 — L6-05 Torque Detection Level 2 Sets the overtorque/undertorque detection level. 100% is equal to the motor rated current in V/f control and the motor rated torque in Open Loop Vector control. 0 to 300 150% A A A 4A5 — L6-06 Torque Detection Time 2 Sets the length of time an overtorque/ undertorque condition must exist before torque detection 2 is recognized by the drive. 0.0 to 10.0 0.1 s A A A 4A6 —