B.2 Parameter Table 346 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M L6-08 Mechanical Weakening (OL5) Detection Operation This function can detect an over/undertorque in a certain speed range as a result of machine fatigue. It is triggered by a certain operation time and uses the OL1 detection settings (L6-01 to L6-03) 0: Mechanical Weakening Detection disabled. 1: Continue running if the speed (signed) is greater than L6-09 (alarm only). 2: Continue running if the speed (not signed) is greater than L6-09 (alarm only). 3: Interrupt drive output when the motor speed (signed) is greater than L6-09 (protection operation). 4:
Interrupt drive output when the motor speed (not signed) is greater than L6-09 (protection operation). 5: Continue running if the speed (signed) is less than L6-09 (alarm only). 6: Continue running if the speed (not signed) is less than L6-09 (alarm only). 7: Interrupt drive output when the motor speed (signed) is less than L6-09 (protection operation). 8: Interrupt drive output when the motor speed (not signed) is less than L6-09 (protection operation). 0 to 8 0 A A A 468 — L6-09 Mechanical Weakening Detection Speed Level • Sets the speed that triggers mechanical weakening detection. • When L6-08 is set for an unsigned value, the absolute value is used even if the setting is negative.
-110.0 to +110.0% 110% A A A 469 — L6-10 Mechanical Weakening Detection Time Sets the time a mechanical weakening has to be detected before an Alarm/Fault is triggered. 0.0 to 10.0 s 0.1 s A A A 46A — L6-11 Mechanical Weakening Detection Start Time Sets the operation time (U1-04) that has to be passed before Mechanical weakening detection is active. 0 to 65535 0 A A A 46B —