omron — n: Advanced Performance Set-Up

B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 351 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M n2: Speed Feedback Detection Control Function Use n2 parameters to configure the Speed Feedback Detection Control function operation. n2-01 Speed Feedback Detection Control (AFR) Gain Sets the internal speed feedback detection control gain in the automatic frequency regulator (AFR). This parameter does not typically require adjustment. Adjust this parameter as follows: If hunting occurs, increase the set value. If response is low, decrease the set value.

0.00 to 10.00 1.00 − A − 584 — Adjust the setting by 0.05 units at a time, while checking the response. n2-02 Speed Feedback Detection Control (AFR) Time Constant Sets the AFR time constant 1. 0 to 2000 50 ms − A − 585 — n2-03 Speed Feedback Detection Control (AFR) Time Constant 2 Sets the AFR time constant 2. Increase the setting if overvoltage occurs during sudden load changes or the speed overshoots during fast acceleration. 0 to 2000 750 ms − A − 586 — n3: High-Slip Braking Use n3 parameters to configure the high-slip braking function.

n3-01 High-Slip Braking Deceleration Frequency Width Sets the output frequency reduction step width when the drive stops the motor using high-slip braking (HSB). If Overvoltage (OV) faults occur during HSB, this parameter may need to be increased. 1 to 20 5% A − − 588 — n3-02 High-Slip Braking Current Limit Sets the current limit during HSB. Higher n3-02 settings will shorten motor stopping times but increase the motor current, and therefore motor heating. 100 to 200 150 % A − − 589 — n3-03 High-Slip Braking Dwell Time at Stop Sets the time the drive will run with minimum frequency (E1-09) at the end of deceleration.

If this time is set too low, the machine inertia can cause the motor to rotate slightly after HSB completion. 0.0 to 10.0 1.0 s A − − 58A — n3-04 High-Slip Braking Overload Time Sets the time required for an HSB overload fault (OL7) to occur when the drive output frequency does not change during an HSB stop. This parameter does not typically require adjustment. 30 to 1200 40 s A − − 58B — n3-13 Overexcitation Deceleration Gain Applies a gain to the V/f pattern during deceleration (L3-04=4). Returns to normal values after ramp to stop or at re-acceleration. To improve the braking power of overexcitation, increase the gain by 1.25 to 1.30. 1.00 to 1.40 1.10 A A − 531 —