B.2 Parameter Table Default setting value is dependent on parameter o2-04, Drive Unit Selection. Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 353 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M n8-54 Voltage Error Compensation Time Constant Sets the time constant for voltage error compensation. Adjust the value when • hunting occurs at low speed. • hunting occurs with sudden load changes. Increase in steps of 0.1 or disable the compensation by setting n8-45 to 0. • oscillations occur ar start. Increase the value in steps of 0.1.
0.00 to 10.00 s 1.00s − − A 56D — n8-55 Load Inertia Sets the ratio between motor and machine inertia. 0: less than 1:10. 1: between 1:10 to 1:30. 2: between 1:30 to 1:50. 3: higher than 1:50. 0 to 3 0 − − A 56E — n8-62 Output Voltage Limit Sets the limit for the output voltage. Adjustment is normally needed only if the input voltage is below the n8-62 set value. In this case set n8-62 to the input voltage. 0.0 to 230.0 200 Vac - - A 57D —