omron — T: Motor Tuning

B.2 Parameter Table ◆ T: Motor Tuning Enter data into the following parameters to tune the motor and drive for optimal performance OYMC TOEP C71060622-01-OY V1000 User Manual 359 No. Name Description Range Def. Control Mode Addr. Hex Pg. V/f O LV P M r1-38 FBD’s Connection Parameter 19 (lower) Parameter 19 for connecting FBD’s (lower). 0 to FFFFH 0 – A A 1865 — r1-39 FBD’s Connection Parameter 20 (upper) Parameter 20 for connecting FBD’s (upper). 0 to FFFFH 0 – A A 1866 — r1-40 FBD’s Connection Parameter 20 (lower) Parameter 20 for connecting FBD’s (lower). 0 to FFFFH 0 – A A 1867 — No. Name Description Range Def. Control Mode Addr. Hex Pg.

V/f O LV P M T1-00 Motor Selection 1/2 Selects which set of motor parameters are used and set during Auto-Tuning. If Motor 2 selection (H1-†† = 16) is not selected, this parameter will not be displayed. 1: 1st Motor - E1 to E2 2: 2nd Motor - E3 to E4 (this selection is not displayed if motor 2 has not been selected) 1, 2 1 A A − 700 — T1-01 Auto-Tuning Mode Selection Selects the Auto-Tuning mode. 0: Rotational Auto-Tuning 2: Stationary Auto-Tuning, Terminal resistance only, 3:

Rotational Auto-Tuning for V/f control (necessary for Energy Savings and Speed Estimation type speed search) 0, 2, 3 2 or 3 in V/f 0 or 2 in OLV 2 for Motor 2 A A − 701 — B T1-02 Motor Rated Power Sets the motor rated power in kilowatts (kW). Note: If motor power is given in horsepower, power in kW can be calculated using the following formula: kW = HP x 0.746. 0.00 to 650.00 0.40 kW A A − 702 — T1-03 Motor Rated Voltage Sets the motor rated voltage in volts (V). 0.0 to 255.5 200.0 V A A − 703 — T1-04 Motor Rated Current Sets the motor rated current in amperes (A). 10 to 200% of drive rated current A A − 704 —