B.2 Parameter Table 366 OYMC TOEP C71060622-01-OY V1000 User Manual No. Name Description Analog Output Level Unit Control Mode Addr. Hex V/f O LV P M U3-17 Cumulative Operation Time at 7th Most Recent Fault Displays the cumulative operation time at the seventh most recent fault. No signal output available 1 h A A A 810E U3-18 Cumulative Operation Time at 8th Most Recent Fault Displays the cumulative operation time at the eighth most recent fault. No signal output available 1 h A A A 811E U3-19 Cumulative Operation Time at 9th Most Recent Fault Displays the cumulative operation time at the ninth most recent fault.
No signal output available 1 h A A A 812 U3-20 Cumulative Operation Time at 10th Most Recent Fault Displays the cumulative operation time at the tenth most recent fault. No signal output available 1 h A A A 813 U4: Maintenance Monitors Use U4 parameters to display drive maintenance information. U4-01 Accumulated Operation Time Displays the cumulative operation time of the drive. The value for the cumulative operation time counter can be set in parameter o4-01. Use parameter o4-02 to determine if the operation time should start as soon as the power is switched on or only while the run command is present. The maximum number displayed is 99999, after which the value is reset to 0.
No signal output avail. 1 h A A A 4C U4-02 Number of Run Commands Displays the number of times the run command is entered. Reset the number of run commands using parameter o4-13. This value will reset to 0 and start counting again after reaching 65535. No signal output avail. A A A 76 U4-03 Cooling Fan Operation Time Displays the cumulative operation time of the cooling fan. The default value for the fan operation time is set to parameter o4-03. This value will reset to 0 and start counting again after reaching 65535. No signal output avail. 1H A A A 67 U4-05 Capacitor Maintenance Displays main circuit capacitor usage time in in percent of their expected performance life.
Parameter o4-06 resets this monitor. No signal output avail. 1% A A A 7C U4-06 Soft Charge Circuit Maintenance Displays the soft charge MC relay maintenance time as a percentage of the estimated product life. Parameter o4-07 resets this monitor. No signal output avail. 1% A A A 7D6 U4-07 IGBT Maintenance Displays IGBT usage time as a percent of expected performance life. Parameter o4-09 resets this monitor. No signal output avail. 1% A A A 7D7