B.2 Parameter Table Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 367 No. Name Description Analog Output Level Unit Control Mode Addr. Hex V/f O LV P M U4-09 LED Check Lights all segments of the LED to verify that the display is working properly. No signal output avail. – A A A 3C U4-10 kWH, Lower 4 Digits Monitors the drive output power. The value is shown as a 9 digit number displayed across two monitor parameters, U4-10 and U4-11. Example: 12345678.9 kWh is displayed as: U4-10: 678.9 kWh U4-11: 12345 MWh Analog monitor: No output signal available. No signal output avail.
kWh A A A 5C U4-11 kWH, Upper 5 Digits MW h A A A 5D U4-13 Peak Hold Current Displays the peak hold current during run. 10 V: Motor rated current 0.01 A A A A 7CF U4-14 Peak Hold Output Frequency Displays the output frequency when operating at the peak hold current. 10 V: Max frequency 0.01 Hz A A A 7D0 U4-16 Motor Overload Estimate (OL1) 100% = OL1 detection level 100% = OL1 detection level 0.1% A A A 7D8 U4-18 Frequency Reference Source Selection Displays the source for the frequency reference as XY-nn. X: indicates which reference is used: 1 = Reference 1 (b1-01) 2 = Reference 2 (b1-15) Y-nn:
indicates the reference source 0-01 = Operator (d1-01) 1-01 = Analog (terminal A1) 1-02 = Analog (terminal A2) 2-02 to 17 = Multi-step speed (d1-02 to 17) 3-01 = MEMOBUS/Modbus comm. 4-01 = Option 5-01 = Pulse Input 6-01 = CASE 7-01 = FBD’s A A A 7DA U4-19 Frequency Reference from MEMOBUS/ Modbus Comm. Displays the frequency reference provided by MEMOBUS/Modbus (decimal) A A A 7DB U4-20 Option Frequency Reference Displays the frequency reference input by an option card (decimal). A A A 7DD