B.2 Parameter Table Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Used as default settings for E1-04 to E1-10 and E2-04 to E2-10 Table B.4 E1-03 V/f Pattern Settings for Drive Capacity: VZAB2P2 to VZAB4P0; VZA22P2 to VZA2015; VZA42P2 to VZA4012 Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Used as default settings for E1-04 to E1-10 and E2-04 to E2-10 Parameter List B OYMC TOEP C71060622-01-OY V1000 User Manual 373 No.
U V/f Control OLV E1-03 − 0 1 2 3 4 5 6 7 8 9 A B C D E F E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120 180 60.0 50.0 E1-05 V 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0 50.0 E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 E1-08 V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0 14.0 13.2 E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 0.5 E1-10 V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0 2.4