B.2 Parameter Table ◆ Default Settings Determined by Drive Capacity (o2-04) and ND/HD Selection (C6-01) Default settings for the following parameters will vary based on drive capacity. Table B.5 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings 374 OYMC TOEP C71060622-01-OY V1000 User Manual No. Description Unit Default Settings − Model VZA − B0P1 B0P2 B0P4 C6-01 Normal/Heavy Duty Sel.
− HD ND HD ND HD ND o2-04 Drive Unit Selection Hex 30 31 32 E2-11 (E4-11, T1-02) Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 b3-06 Speed Search current 1 − 1 1 1 1 1 1 b8-04 Energy saving coefficient − 481.7 356.9 356.9 288.2 288.2 223.7 C6-02 Carrier frequency − 4 7 4 7 4 7 E2-01 (E4-01, T1-04) Motor rated current A 0.6 1.1 1.1 1.9 1.9 3.3 E2-02 (E4-02) Motor rated slip Hz 2.5 2.6 2.6 2.9 2.9 2.5 E2-03 (E4-03) Motor no load current A 0.4 0.8 0.8 1.2 1.2 1.8 E2-05 (E4-05) Motor line-to-line resistance Ω 35.98 20.56 20.56 9.842 9.842 5.156 E2-06 (E4-06) Motor leakage inductance % 21.6 20.1 20.1 18.2 18.2 13.8 E2-10 (E4-10) Motor Iron Loss W 6 11 11 14 14 26 E5-01 Motor code hex FFFF FFFF FFFF FFFF 0002 0002 L2-02 Momentary power loss ride- through time s 0.1 0.1 0.1 0.1 0.1 0.1 L2-03 Mom.
power loss base block time s 0.2 0.2 0.2 0.2 0.2 0.3 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 L2-05 UV detection voltage V dc 160 160 160 160 160 160 L3-24 Motor acceleration time s 0.178 0.178 0.178 0.178 0.178 0.142 L8-02 Overheat alarm level °C 115 115 115 115 110 110 L8-09 Ground fault selection − 0 0 0 0 0 0 L8-38 Carrier freq. reduction sel. − 1 1 1 1 1 1 n1-03 Hunting Prev. Time Const. ms 10 10 10 10 10 10