omron — Default Settings Determined by Drive Capacity (o2-04) and ND/HD Selection (C6-01)

B.2 Parameter Table OYMC TOEP C71060622-01-OY V1000 User Manual 377 No.

Description Unit Default Settings − Model VZA† − 22P2 24P0 25P5 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND o2-04 Drive Unit Selection Hex 66 68 6A E2-11 (E4-11, T1-02) Motor rated power kW 2.2 3.0 3.7 5.5 5.5 7.5 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5 b8-04 Energy saving coefficient − 156.8 136.4 122.9 94.75 94.75 72.69 C6-02 Carrier frequency − 3 7 3 7 3 7 E2-01 (E4-01, T1-04) Motor rated current A 8.5 11.4 14 19.6 19.6 26.6 E2-02 (E4-02) Motor rated slip Hz 2.9 2.7 2.73 1.5 1.5 1.3 E2-03 (E4-03) Motor no load current A 3.0 3.7 4.5 5.1 5.1 8.0 E2-05 (E4-05) Motor line-to-line resistance Ω 1.601 1.034 0.771 0.399 0.399 0.288 E2-06 (E4-06) Motor leakage inductance % 18.4 19 19.6 18.2 18.2 15.5 E2-10 (E4-10) Motor Iron Loss W 77 91 112 172 172 262 E5-01 Motor Code hex 0006 0006 0008 0008 FFFF FFFF L2-02 Momentary power loss ride-through time s 0.5 0.5 1 1 1.0 1.0 L2-03 Momentary power loss base block time s 0.5 0.5 0.6 0.7 0.7 0.8 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 B L2-05 UV detection voltage V dc 190 190 190 190 190 190 L3-24 Motor acceleration time s 0.145 0.145 0.154 0.168 0.168 0.175 L8-02 Overheat alarm level °C 100 100 110 110 115 115 L8-09 Ground fault selection − 0 0 0 0 1 1 L8-35 Installation Method Sel.

− 0 0 0 0 2 2 L8-38 Carrier frequency reduction selection − 1 1 1 1 2 2 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10