omron — Default Settings Determined by Drive Capacity (o2-04) and ND/HD Selection (C6-01)

B.2 Parameter Table 378 OYMC TOEP C71060622-01-OY V1000 User Manual No.

Description Unit Default Settings − Model VZA† − 27P5 2011 2015 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND o2-04 Drive Unit Selection Hex 6B 6D 6E E2-11 (E4-11, T1-02) Motor rated power kW 7.5 11.0 11.0 15.0 15.0 18.5 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5 b8-04 Energy saving coefficient − 72.69 70.44 70.44 63.13 63.13 57.87 C6-02 Carrier frequency − 3 7 3 7 3 7 E2-01 (E4-01, T1-04) Motor rated current A 26.6 39.7 39.7 53 53 65.8 E2-02 (E4-02) Motor rated slip Hz 1.3 1.7 1.7 1.6 1.6 1.67 E2-03 (E4-03) Motor no load current A 8.0 11.2 11.2 15.2 15.2 15.7 E2-05 (E4-05) Motor line-to-line resistance Ω 0.288 0.230 0.230 0.138 0.138 0.101 E2-06 (E4-06) Motor leakage inductance % 15.5 19.5 19.5 17.2 17.2 15.7 E2-10 (E4-10) Motor Iron Loss W 262 245 245 272 272 505 E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF L2-02 Momentary power loss ride-through time s 1.0 1.0 2.0 2.0 2.0 2.0 L2-03 Momentary power loss base block time s 0.8 0.9 0.9 1.0 1.0 1.0 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.6 0.6 L2-05 UV detection voltage V dc 190 190 190 190 190 190 L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317 L8-02 Overheat alarm level °C 121 121 120 120 120 120 L8-09 Ground fault selection − 1 1 1 1 1 1 L8-35 Installation Method Sel.