C.1 MEMOBUS/Modbus Basic Set-Up C.1 MEMOBUS/Modbus Basic Set-Up Serial communication can be performed with Program Logic Controllers (PLCs) or similar master devices using the MEMOBUS/Modbus protocol. ◆ MEMOBUS/Modbus Communication Configuration MEMOBUS/Modbus communication is configured using 1 master (PLC) and a maximum of 31 slaves. Serial communication between master and slave is normally initiated by the master and responded to by the slaves. The master performs serial communication with one slave at a time. Consequently, the slave address of each slave must be initially set, so that the master can perform serial communication using that address.

Slaves receiving commands from the master perform the specified functions, and send a response back to the master. Figure C.1 Master Slaves AC Drive AC Drive AC Drive Figure C.1 Example of Connections between Master and Drive 390 OYMC TOEP C71060622-01-OY V1000 User Manual