C.1 MEMOBUS/Modbus Basic Set-Up ◆ Communication Specifications The MEMOBUS/Modbus communication specifications are explained in Table C.1 . Table C.1 MEMOBUS/Modbus Communication Specifications ◆ Communication Connection Terminal MEMOBUS/Modbus communication uses the following terminals: S+, S-, R+, and R-. The terminating resistor must be turned ON only if the Drive is at the very end of the serial communication chain. Set the terminating resistor by turning ON pin 1 of switch S2.

Figure C.2 S+ + S- - Network Communications RS-422A or RS-485 R+ R- Switch 1 Terminating resistor (1/2W, 110 Ohms) C Figure C.2 MEMOBUS/Modbus Switch Table C.2 MEMOBUS/Modbus Switch Settings OYMC TOEP C71060622-01-OY V1000 User Manual 391 Item Specifications Interface RS-422, RS-485 Communications Cycle Asynchronous (Start-stop synchronization) Communications Parameters Baud rate: Select from 1200 to 115200 bps. Data length: 8 bits fixed Parity: Select from even, odd, or none. Stop bits:

1 bit selected Communications Protocol MEMOBUS/Modbus RTU Number of Connectable Units 31 units maximum S2 Position Description ON Internal terminal resistance ON OFF Internal terminal resistance OFF (no terminal resistance); default setting