2.2 Mechanical Installation ◆ Installation Orientation and Spacing Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling. Figure 2.1 A B B A – Correct B – Incorrect Figure 2.1 Correct Installation Orientation ■ Single Drive Installation To maintain sufficient space for airflow and wiring, refer to Figure 2.2 . Install the heatsink against a closed surface to avoid diverting cooling air around the heatsink. Figure 2.2 Side Clearance A A Top/Bottom Clearance C B C A – 30 mm minimum C – 100 mm minimum B – Airflow direction Figure 2.2 Correct Installation Spacing Note: