omron — Installation Orientation and Spacing

2.2 Mechanical Installation ■ Multiple Drive Installation When installing multiple drives into the same enclosure panel, mount the drives according to Figure 2.2 . When mounting drives with a minimum side-by-side clearance of 2 mm according to Figure 2.3 , derating must be considered and parameter L8-35 must be set. Refer to Parameter List on page 293 . Mechanical Installation Figure 2.3 2 mm A B B C 2 D C A – Line up the tops of the drives. C – 100 mm minimum B – 30 mm minimum D – Airflow direction Figure 2.3 Space Between Drives (Side-by-Side Mounting) Note: When installing drives of different sizes into the same enclosure panel, the tops of the drives should line up.

Leave space between the top and bottom of stacked drives for cooling fan replacement if required. Using this method, it is possible to replace the cooling fans later. NOTICE: When drives with IP20/NEMA Type 1 enclosures are mounted side-by-side, the top covers of all drives must be removed as shown in the figure below. Figure 2.4 Figure 2.4 IP20/NEMA 1 Side-by-Side Mounting in Enclosure OYMC TOEP C71060622-01-OY V1000 User Manual 41