C.1 MEMOBUS/Modbus Basic Set-Up Figure C.4 Figure C.4 Control Circuit Terminal Block Configuration ◆ Communication Set-Up Procedure Use the following procedure to communicate with the PLC. 1. Turn OFF the input to the drive power and connect the communication cable between the PLC (or other master device) and the drive. 2. Turn ON the input power to the drive. 3. Set the required communication parameters (H5-01 to H5-07) using the Digital Operator. 4. Turn OFF the input to the drive power, and check that the Digital Operator display has completely extinguished. 5. Turn ON the input power to the drive once again. 6. Perform communication with the master device.
Network Communications C OYMC TOEP C71060622-01-OY V1000 User Manual 393