omron — Communication Set-Up Procedure

C.1 MEMOBUS/Modbus Basic Set-Up Table C.4 Serial Communication Related Parameters 394 OYMC TOEP C71060622-01-OY V1000 User Manual Parameter No. Parameter Name Digital Operator Display Description Setting Range Factory Setting b1-01 Frequency Reference Selection Reference Source Selects the frequency reference input source. 0: Operator - Digital preset speed U1-01 or d1-01 to d1-17. 1: Terminals - Analog input terminal A1 (or terminal A2 based on parameter H3-09). 2: Serial Com - MEMOBUS/Modbus RS-422/485 terminals R+, R-, S+ and S-. 3: Option PCB 4: Pulse Input (Terminal RP) 0 to 4 1 b1-02 Run Command Selection Run Source Selects the run command input source. 0:

Operator - RUN and STOP keys on the digital operator. 1: Terminals - Contact closure on terminals S1 or S2. 2: Serial Com - MEMOBUS/Modbus RS-422/485 terminals R+, R-, S+ and S-. 3: Option PCB. 0 to 3 1 H5-01 Drive Node Address Serial Comm Adr Selects drive station node number (address) for MEMOBUS/ Modbus terminals R+, R-, S+, S-. Cycle power for the setting to take effect. 0 to 20 Hex 1F H5-02 Communication Speed Selection Serial Baud Rate Selects the baud rate for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0: 1200 bps 1: 2400 bps 2: 4800 bps 3: 9600 bps 4: 19200 bps 5: 38400 bps 6: 57600 bps 7: 76800 bps 8:

115200 bps 0 to 8 3 H5-03 Communication Parity Selection Serial Com Sel Selects the communication parity for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0: No parity 1: Even parity 2: Odd parity 0 to 2 0 H5-04 Stopping Method After Communication Error Serial Fault Sel Selects the stopping method when a communication time-out fault (CE) is detected. 0: Ramp to stop 1: Coast to stop 2: Fast-stop 3: Alarm only 0 to 3 3