omron — Communication Set-Up Procedure

C.1 MEMOBUS/Modbus Basic Set-Up MEMOBUS/Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02: • Monitor the operation status of the drive • Set and read drive parameters • Reset faults • Input multi-function digital input commands • Control multi-function digital and analog outputs. Note: An OR operation is performed between the multi-function command input from the master device and the command input from multi-function digital input terminals S3 to S6. Network Communications C OYMC TOEP C71060622-01-OY V1000 User Manual 395 Parameter No.

Parameter Name Digital Operator Display Description Setting Range Factory Setting H5-05 Communication Fault Detection Selection Serial Flt Dtct Enables or disables the communications time-out fault (CE). 0: Disabled - A communication loss will not cause a communication fault. 1: Enabled - If communication is lost for more than two seconds, a CE fault will occur. 0 or 1 1 H5-06 Drive Transmit Wait Time Transmit WaitTIM Set the delay time from when the drive receives data to when the drive sends data. 5 to 65 5ms H5-07 RTS Control Selection RTS Control Sel Enables or disables "request to send" (RTS) control: 0: Disabled - RTS is always on. 1: Enabled - RTS turns on only when sending. 0 to 1 1