omron — CE Low Voltage Directive Compliance

D.2 European Standards ■ Installing Fuses on the Input Side Install recommended UL-approved fuses at the main power input of the drive. Select fuses according to Table D.1 .

Table D.1 Recommended Input Fuse Selection 402 OYMC TOEP C71060622-01-OY V1000 User Manual Drive Model VZA Time Delay/ Class RK5 Fuses 600 Vac, 200 kAIR Fuse Ampere Rating Non-Time Delay/ Class T Fuses 600 Vac, 200 kAIR 200 V Class Single-Phase Drives B0P1 TRS5R 5 Contact your OYMC sales representative B0P2 TRS10R 10 B0P4 TRS20R 20 B0P7 TRS35R 35 B1P5 TRS50R 50 B2P2 TRS60R 60 B4P0 Contact your OYMC sales representative 200 V Class Three-Phase Drives 20P1 TRS5R 5 Contact your OYMC sales representative 20P2 TRS5R 5 20P4 TRS10R 10 20P7 TRS15R 15 21P5 TRS25R 25 22P2 TRS35R 35 24P0 TRS60R 60 25P5 Not Available 70 A6T70 27P5 100 A6T100 2011 150 A6T150 2015 200 A6T200 400 V Class Three-Phase Drives 40P2 TRS2.5R 2.5 Contact your OYMC sales representative 40P4 TRS5R 5 40P7 TRS10R 10 41P5 TRS20R 20 42P2 TRS20R 20 43P0 TRS20R 20 44P0 TRS30R 30