omron — EMC Guidelines Compliance

D.2 European Standards When installing IP20/Open-Chassis drives, use an enclosure that prevents foreign material from entering the drive from above or below. ■ Guarding Against Harmful Materials The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded systems, contact your dealer for instructions. ■ Grounding ◆ EMC Guidelines Compliance This drive is tested according to European standards EN61800-3 and it complies with the EMC guidelines. ■ EMC Filter Installation The following conditions must be met to ensure continued compliance with guidelines. Refer to EMC Filters on page 407 for EMC filter selection.

Installation Method Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive also comply with EMC guidelines. 1. Install an EMC noise filter to the input side specified by OYMC for compliance with European standards. 2. Place the drive and EMC noise filter in the same enclosure. 3. Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit. 4. Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.

Standards Compliance D OYMC TOEP C71060622-01-OY V1000 User Manual 403 Drive Model VZA Time Delay/ Class RK5 Fuses 600 Vac, 200 kAIR Fuse Ampere Rating Non-Time Delay/ Class T Fuses 600 Vac, 200 kAIR 45P5 Not Available 50 A6T50 47P5 60 A6T60 4011 70 A6T70 4015 80 A6T80