omron — Drive Motor Overload Protection

D.3 UL Standards Table D.7 Overload Protection Settings Disable the electronic overload protection (L1-01 = 0: Disabled) and wire each motor with its own motor thermal overload when connecting the drive to more than one motor for simultaneous operation. Enable the motor overload protection (L1-01 = “1”, “2”, or “3”) when connecting the drive to a single motor unless there is another means of preventing motor thermal overload. The electronic thermal overload function causes an OL1 fault, which shuts off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated as long as the drive is powered up.

Setting L1-01 = 1 selects a motor with limited cooling capability below rated (base) speed when running at 100% load. The OL1 function derates the motor when it is running below base speed. Setting L1-01 = 2 selects a motor capable of cooling itself over a 10:1 speed range when running at 100% load. The OL1 function derates the motor when it is running at 1/10 or less of its rated speed. Setting L1-01 = 3 selects a motor capable of cooling itself at any speed — including zero speed — when running at 100% load. The OL1 function does not derate the motor at any speed. Setting L1-01 = 4 selects protection for a PM motor. ■ L1-02 Motor Overload Protection Time Setting Range:

0.1 to 20.0 Minutes Factory Default: 8.0 Minutes The L1-02 parameter sets the allowed operation time before the OL1 fault occurs when the drive is running at 60 Hz and 133% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the set of OL1 curves up the Y-axis of the diagram below but will not change the shape of the curves. 414 OYMC TOEP C71060622-01-OY V1000 User Manual Setting Description 0 Disabled 1 Std. Fan Cooled ( 2 Standard Blower Cooled (10:1 motor) 3 Vector Motor (1000:1 motor) 4 PM motor