omron — Wire Gauges and Tightening Torque

3.6 Main Circuit Wiring 3.6 Main Circuit Wiring This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit of the drive. NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. Electrical Installation ◆ Main Circuit Terminal Functions Table 3.1 Main Circuit Terminal Functions 3 ◆ Wire Gauges and Tightening Torque Select the appropriate wires and crimp terminals from Table 3.2 through Table 3.4 . Note: 1.

Wire gauge recommendations based on drive continuous current ratings using 75 ° C 600 Vac vinyl- sheathed wire assuming ambient temperature within 30 ° C and wiring distance less than 100 m. 2. Terminals +1, +2, –, B1 and B2 are for connecting optional devices such as a DC reactor or braking resistor. Do not connect other non-specified devices to these terminals. • Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop:

• Line drop voltage (V) = 3 x wire resistance ( Ω /km) x wire length (m) x current (A) x10 -3 OYMC TOEP C71060622-01-OY V1000 User Manual 59 Terminal Type Function Reference R/L1 Main circuit power supply input Connects line power to the drive. Drives with single phase 200 V input power use terminals R/L1 and S/L2 only (T/L3 must not be used). 54 S/L2 T/L3 U/T1 Drive output Connects to the motor. 63 V/T2 W/T3 B1 Braking resistor Available for connecting a braking resistor or the braking resistor unit option. 78 B2 +1 DC reactor connection These terminals are shorted at shipment. Remove the shorting bar between +1 and +2 when connecting to this terminal.

267 +2 +1 DC power supply input For connecting a DC power supply. - – (2 terminals) Ground Grounding Terminal For 200 V class: 100 Ω or less For 400 V class: 10 Ω or less 63