3.7 Control Circuit Wiring Figure 3.19 Push down to open the terminal Turn the wire ~ 45 and pull it out of the terminal. Electrical Installation Use a screwdriver with a blade width of max 2.5 mm and a thickness of max 0.4 mm Terminal Board Control Wires Figure 3.19 Removing Wires from the Terminal Board 3 Figure 3.20 A F C D E B A – Drive side D – Control device side B – Connect shield to ground terminal of drive.
E – Shield sheath (Insulate with tape) C – Insulation F – Shield Figure 3.20 Preparing the Ends of Shielded Cables When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires and ground the shield of twisted-pair wires to the ground terminal of the drive. NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance. OYMC TOEP C71060622-01-OY V1000 User Manual 71