3.7 Control Circuit Wiring NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines. Improper wiring practices could result in drive or equipment malfunction or nuisance trips. NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply. NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could result in drive or equipment malfunction due to short circuit. NOTICE:
Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or equipment malfunction or nuisance trips. Prepare the wire ends for connecting them to the terminal board like shown in Figure 3.20 . Use ferrules like specified above or solid wires. The stripping length for solid wires is 8 mm. NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or equipment malfunction due to electrical interference. Connect control wires like shown in Figure 3.18 .
Figure 3.18 Push wire end into terminal Control Wires Terminal Board Figure 3.18 Connecting Wires to the Control Terminals To disconnect control wires from the terminals use the procedure described in Figure 3.19 . Grasp the wire where it enters the terminal with a pair of pliers, then use a straight-edge screw driver to release the terminal and pull the wire out. If it fits tightly, e.g. if ferrules are used, turn the wire for about 45 ° and then pull it gently out. Use this procedure to remove the wire jumper between terminals HC, H1 and H2 that is preinstalled at shipping. 70 OYMC TOEP C71060622-01-OY V1000 User Manual