3.7 Control Circuit Wiring Table 3.9 Wire Size Specifications (Same for All Models) Electrical Installation ■ Ferrule-Type Wire Terminations Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX ZA-3, a crimping tool manufactured by PHOENIX CONTACT. Figure 3.17 3 Table 3.10 Ferrule Terminal Types and Sizes Figure 3.17 Ferrule Dimensions ◆ Wiring Procedure This section describes the proper procedures and preparations for wiring the terminal board. WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result in death or serious injury. NOTICE:
Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference. OYMC TOEP C71060622-01-OY V1000 User Manual 69 Terminal Bare Wire Terminal Ferrule-Type Terminal Wire Type Applicable wire size mm2 (AWG) Recommended wire size mm2 (AWG) Applicable wire size mm2 (AWG) Recommended wire size mm2 (AWG) S1-S6, SC, RP, +V, A1, A2, AC, HC, H1, H2, P1, P2, PC, MP, AM, AC, S+, S-, R+, R-, IG, MA, MB, MC Stranded wire: 0.2 to 1.0 (24 to 16) Solid wire:
0.2 to 1.5 (24 to 16) 0.75 (18) 0.25 to 0.5 (24 to 20) 0.5 (20) Shielded line, etc. d1 mm 8 L d2 d2 Size mm2 (AWG) Type L (mm) d1 (mm) d2 (mm) Manufacturer 0.25 (24) AI 0.25-8YE 12.5 0.8 1.8 PHOENIX CONTACT 0.34 (22) AI 0.34-8TQ 10.5 0.8 1.8 0.5 (20) AI 0.5-8WH or AI 0.5-8OG 14 1.1 2.5