3.11 Braking Resistor Figure 3.27 Thermal relay Braking resistor Power supply MCCB MC R/L1 B1 B2 S/L2 T/L3 U/T1 V/T2 W/T3 Motor OFF THRX MC ON MC THRX SA Drive Electrical Installation Thermal relay switch for external braking resistor TRX MC SA TRX MA MC SA Figure 3.27 Connecting a Braking Resistor 4. Follow manufacturer instructions to connect the resistor unit to the drive using proper wire gauge according to local electrical codes. Power leads for the remote mount resistors generate high levels of electrical noise; group these signal leads separately. 5. Mount the resistor unit on a noncombustible surface.

Maintain minimum side and top clearances according to resistor manufacturer instructions. Fault contact 3 WARNING! Fire Hazard. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive or braking resistors to metal or other noncombustible material. ■ Adjustments 7. Set parameter L3-04 = “0” or “3” to disable stall prevention during deceleration. Set parameter L8-01= “1” to enable overheat protection when using Yaskawa heatsink mounted braking resistor. Set L8-01 = “0” for other braking resistor types. Set parameter L3-04 = “3” to generate the shortest possible deceleration time. Table 3.16 Braking Resistor Settings 6.

Reinstall drive covers and resistor covers, if provided. Select either 0 or 3. This setting cannot be used in OLV control for PM motor. ■ Operation Check 8. Operate the system and verify the required deceleration rate is obtained during dynamic braking or stopping. OYMC TOEP C71060622-01-OY V1000 User Manual 79 Parameter Settings L8-01: Internal Dynamic Braking Resistor Protection selection 0: Disabled. The drive will not provide overheat protection. Supply separate means of overheat protection. 1: Enabled. Braking Resistor is protected from overheat. L3-04: Stall Prevention During Deceleration 0: Stall prevention disabled. 3: Stall prevention enabled with a braking resistor.