omron — 3.12 Wiring Checklist

3.12 Wiring Checklist Electrical Installation 3 OYMC TOEP C71060622-01-OY V1000 User Manual 81 No. Item Page 14 Set up overload protection circuits when running multiple motors from a single drive. Power supply Drive MC1 OL1 M1 MC2 OL2 M2 MCn OLn Mn MC1 - MCn ... magnetic contactor OL1 - OLn ... thermal relay Note: Close MC1 through MCn before operating the drive. 15 If using a braking resistor or dynamic braking resistor unit, install a magnetic contactor. Properly install the resistor, and ensure that overload protection shuts off the power supply. 78 16 Verify phase advancing capacitors are NOT installed on the output side of the drive.

Control circuit wiring 17 Use twisted-pair cables for all drive control circuit wiring. 65 18 Ground the shields of shielded wiring to the GND terminal. 74 19 If using a 3-wire sequence, properly set parameters for multi-function contact input terminals S1 through S6, and properly wire control circuits. 53 20 Properly wire any option cards. 275 21 Check for any other wiring mistakes. Only use a multimeter to check wiring. - 22 Properly fasten the control circuit terminal screws in the drive. Refer to Table 3.2, Table 3.3 or Table 3.4. 59 23 Pick up all wire clippings. 24 Ensure that no frayed wires on the terminal block are touching other terminals or connections.

25 Properly separate control circuit wiring and main circuit wiring. 26 All signal line wiring should not exceed 50 m. 27 Safe Disable input wiring should not exceed 30 m.