4.3 The Drive and Programming Mode Drive Mode ■ • • Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.). • View information on an alarm. • View a history of alarms that have occurred. Note: Select "Drive Mode" when running. The mode can be switched to any mode (program mode, etc.) other than drive mode while the drive is stopped. However, the drive cannot be operated in other modes. Return the mode to "Drive Mode" after completing periodic inspection. Figure 4.4 illustrates changing the default frequency reference of F 0.00 (0 Hz) to F 6.00 (6 Hz) while in Drive Mode. This example assumes the drive is set to LOCAL.

Figure 4.4 Frequency reference display at power up STOP Press to select LOCAL Press to select the digit to the right Press until the frequency reference becomes 6 Hz Note: The drive will not accept a frequency reference set value unless the ENTER key is pressed after the frequency reference is entered. This feature prevents accidental setting of the frequency reference. By setting o2-05 (Frequency Reference Setting Method Selection) to 1 (Enabled), the drive will accept the frequency reference while it is being adjusted on the digital operator.