omron — Switching Between LOCAL and REMOTE

4.3 The Drive and Programming Mode The example below is continued from page 98 . Here, parameter C1-01 is accessed using the Verify Menu and is changed again to 20.0 s. To check the list of edited parameters: Start-Up Programming & Operation 4 ◆ Switching Between LOCAL and REMOTE Entering the run command using the LED operator is referred to as LOCAL, while entering the run command from an external device via the control circuit terminals or network option card is referred to as Remote. WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury.

Be sure all personnel are clear of rotating machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode. There are three ways to switch between LOCAL and REMOTE. Note: 1. After selecting LOCAL, LO/RE will remain lit. 2. The drive will not allow the user to switch between LOCAL and REMOTE during run. ■ Using the LO/RE Key on the LED Operator OYMC TOEP C71060622-01-OY V1000 User Manual 99 Step Dis play/Result 1. Turn on the power to the drive. The initial display appears. ⇒ 2. Press until the display reads, “Verify.” ⇒ Press to enter the list of parameters that have been edited 3. from their original default settings. Scroll through the list by pressing the key.

⇒ 4. Press the key until C1-01 appears. ⇒ 5. Press the key to access the setting value.(number farthest to the left flashes) ⇒ Step Disp lay/Result 1. Turn on the power to the drive. The initial display appears. ⇒