VLT ® 2900 Series in Closed loop is programmed in parameter 416 Proc- ess units . Set the required value within the feedback range (pa- rameter 414 Minimum feedback, FB MIN and 415 Max- imum feedback, FB MAX ). 0 (OFF) - 100 Hz 0 Hz Some systems call for some output frequencies to be avoided because of mechanical resonance problems in the system. In parameters 230-231 Frequency by- pass these output frequencies can be programmed. In this parameter a bandwidth can be defined on either side of these frequencies. The frequency set in this parameter will be centered around parameters 230 Frequency bypass 1 and 231 Frequency bypass 2 .

Programming 0 - 1000 Hz 0.0 Hz Some SYSTEMs call for some output frequencies to be avoided because of mechanical resonance prob- lems in the SYSTEM. Enter the frequencies to be avoided. See also param- eter 229 Frequency bypass, bandwidth . = factory setting, () = display text, [] = value for use in communication via serial communication port MG.29.A3.02 - VLT ® is a registered Danfoss trademark 35 Description of choice: 229 Frequence bypass, bandwidth (FREQ BYPASS B.W.) Value: Function: Description of choice: 230 Frequency bypass 1 (FREQ. BYPASS 1) 231 Frequency bypass 2 (FREQ. BYPASS 2) Value: Function: Description of choice: