VLT ® 2900 Series Inputs and outputs 1. All functions on terminal 18 and 19 are controlled by an interrupter, which means that the repetitive accu- racy of the response time is constant. Can be used for start/stop, setup switch and especially for changing digital preset, i.e. to obtain a reproducable stop point when using creep speed. No operation is selected if the frequency converter is not to react to signals transmitted to the terminal. Reset resets the frequency converter after an alarm; however, a few alarms cannot be reset (trip locked) without first disconnecting the mains supply and re- connecting it. See table under List of warnings and alarms .
Reset is activated on the leading edge of the signal. In these parameters 302-307 Digital inputs it is possi- ble to choose between the different enabled functions related to the digital inputs (terminals 18-33). Coasting stop inverse is used for making the frequency converter "let go" of the motor immediately (output = factory setting, () = display text, [] = value for use in communication via serial communication port 36 MG.29.A3.02 - VLT ® is a registered Danfoss trademark Digital inputs Term. no. 181 191 27 29 33 par. no. 302 303 304 305 307 Value:
No function (NO OPERATION) [0] [0] [0] [0] [0] Reset (RESET) [1] [1] [1] [1] [1] Coasting stop inverse (MOTOR COAST INVERSE) [2] [2] [2] [2] [2] Reset and coasting inverse (RESET AND COAST INV.) [3] [3] [3] [3] [3] Quick-stop inverse (QUICK-STOP INVERSE) [4] [4] [4] [4] [4] DC braking inverse (DC-BRAKE INVERSE) [5] [5] [5] [5] [5] Stop inverse (STOP INVERSE) [6] [6] [6] [6] [6] Start (START) [7] [7] [7] [7] [7] Pulse start (LATCHED START) [8] [8] [8] [8] [8] Reversing (REVERSING) [9] [9] [9] [9] [9] Reversing and start (START REVERSING) [10] [10] [10] [10] [10] Start clockwise (ENABLE FORWARD) [11] [11] [11] [11] [11] Start anti-clockwise (ENABLE REVERSE) [12] [12] [12] [12] [12] Jog (JOGGING) [13] [13] [13] [13] [13] Freeze reference (FREEZE REFERENCE) [14] [14] [14] [14] [14] Freeze output frequency (FREEZE OUTPUT) [15] [15] [15] [15] [15] Speed up (SPEED UP) [16] [16] [16] [16] [16] Speed down (SPEED DOWN) [17] [17] [17] [17] [17] Catch-up (CATCH-UP) [19] [19] [19] [19] [19] Slow-down (SLOW-DOWN) [20] [20] [20] [20] [20] Ramp 2 (RAMP 2) [21] [21] [21] [21] [21] Preset ref, LSB (PRESET REF, LSB) [22] [22] [22] [22] [22] Preset ref, MSB (PRESET REF, MSB) [23] [23] [23] [23] [23] Preset reference on (PRESET REFERENCE ON) [24] [24] [24] [24] [24] Thermistor (THERMISTOR) [25] [25] [25] [25] Precise stop, inverse (PRECISE STOP INV.) [26] [26] Precise start/stop (PRECISE START/STOP) [27] [27] Pulse reference (PULSE REFERENCE) [28] Pulse feedback (PULSE FEEDBACK) [29] Pulse input (PULSE INPUT) [30] Selection of Setup, lsb (SETUP SELECT LSB) [31] [31] [31] [31] [31] Selection of Setup, msb (SETUP SELECT MSB) [32] [32] [32] [32] [32] Reset and start (RESET AND START) [33] [33] [33] [33] [33] Pulse counter start (PULSE COUNTER START) [34] [34] Description of choice:
Function: