Danfoss — VLT 2900 Manual

VLT ® 2900 Series Set the required frequency. Counter stop with reset [1]. After each precise stop the number of pulses counted during ramp down 0 Hz is reset. Counter stop without reset [2]. The number of pulses counted during ramp down to 0 Hz is deducted from the counter value in parameter 344. Precise ramp stop (normal) [0] Counter stop with reset (Count stop reset) [1] 0 - 999999 Counter stop without reset (Count stop no reset) [2] 100000 pulses Speed-compensated stop (Spd cmp stop) [3] In this parameter you can select the counter value to be used in the integrated precise stop function (pa- rameter 343). Speed-compensated counter stop with reset (Spd cmp cstop w.

res) [4] Speed-compensated counter stop without re- set (Spd cmp cstop no res) [5] The factory setting is 100000 pulses. The highest fre- quency (max. resolution) that can be registered at terminal 33 is 67.6 kHz. In this parameter you select which stop function is per- formed in response to a stop command. All six data selections contain a precise stop routine, thus ensur- ing a high level of repeat accuracy. The selections are a combination of the functions de- scribed below. 0 ms - 100 ms NB! Pulse start [8] may not be used together with the precise stop function. In this parameter the user can set the SYSTEM's delay time (Sensor, PLC, etc.).

If you are running speed- compensated stop, the delay time at different frequen- cies has a major influence on the way in which you stop. 10 ms Precise ramp stop [0] is selected to achieve high re- petitive precision at the stopping point. Counter stop . Once it has received a pulse start signal the frequency converter runs until the number of pul- ses programmed by the user have been received at input terminal 33. In this way an internal stop signal will activate the normal ramp down time (parameter 208). The counter function is activated (starts timing) at the flank of the start signal (when it changes from stop to start). Speed compensated stop .

To stop at precisely the same point, regardless of the present speed, a stop signal received is delayed internally when the present speed is lower than the maximum speed (set in pa- rameter 202). Reset . Counter stop and Speed-compensated stop can be combined with or without reset. The factory setting is 10 ms. This means that it is as- sumed that the total delay from the Sensor, PLC and other hardware corresponds to this setting. NB! Only active for speed-compensated stop. = factory setting, () = display text, [] = value for use in communication via serial communication port 44 MG.29.A3.02 - VLT ® is a registered Danfoss trademark Description of choice:

343 Precise stop function (Precise stop) Value: 344 Counter value (Pulse count pre.) Value: Function: Description of choice: Function: 349 Speed comp delay (SPEED COMP DELAY) Value: Function: Description of choice: Description of choice: