Danfoss — VLT 2900 Manual

VLT ® 2900 Series Special functions This parameter makes it possible to select whether re- set and restart after a trip are to be manual or whether the frequency converter is to be reset and restarted automatically. Furthermore, it is possible to select the number of times a restart is to be attempted. The time between each attempt is set in parameter 406 Auto- matic restart time . Off (off) [0] Resistor brake (Resistor) [1] AC brake (AC Brake) [4] Load sharing (load sharing) [5] If Manual reset [0] is selected, reset is to be carried out via the [STOP/RESET] key, a digital input or serial communication.

If the frequency converter is to carry out an automatic reset and restart after a trip, select data value [1], [3] or [10]. If Reset at power-up [11] is selected, the frequency converter will carry out a reset if there has been a fault in connection with the mains failure. Factory setting depends on unit type. Resistor brake [1] is selected if the frequency converter has an integral brake transistor and brake resistor is connected to terminals 81, 82. A higher intermediate circuit voltage is permitted during braking (generated operation) when a brake resistor is connected. AC brake [4] can be selected to improve braking with- out using brake resistors.

Please note that AC brake [4] is not as effective as Resistor brake [1]. The motor may start without warning. Select Resistor brake [1] if a brake resistor is connec- ted. Select AC brake [4] if short-term generated loads oc- cur. See parameter 144 Gain AC brake to set the brake. Programming 0 - 10 sec. 5 sec. Select Load sharing [5] if this is used. This parameter allows setting of the time from tripping until the automatic reset function begins. It is assumed that automatic reset has been selected in parameter 405 Reset function . NB! A change of selection will not become ac- tive until the mains voltage has been dis- connected and reconnected. Set the required time.

Manual reset (manual reset) [0] Automatic reset x 1 (AUTOMATIC x 1) [1] 0 - 60 sec. (61=OFF) Automatic reset x 3 (AUTOMATIC x 3) [3] OFF When the frequency converter registers that the output current has reached the current limit I LIM (parameter 221 Current limit ) and remains there for the preset time, it is disconnected. Can be used to protect the application, like the ETR will protect the motor if se- lected. Automatic reset x 10 (AUTOMATIC x 10) [10] Reset at power-up (RESET AT POWER UP) [11] = factory setting, () = display text, [] = value for use in communication via serial communication port MG.29.A3.02 - VLT ® is a registered Danfoss trademark 45 Function:

400 Brake function (Brake function) Value: Description of choice: Function: Description of choice: 406 Automatic restart time (autorestart time) Value: Function: Description of choice: 405 Reset function (reset mode) Value: 409 Trip delay overcurrent, ILIM (trip delay cur.) Value: Function: