Lenze — 4.6.5 Devices in the range 145 695 A ( 75 400 kW)

Single-axis controllers Wiring Devices in the range 145 ... 695 A (75 ... 400 kW) 4 4.6 4.6.5 External brake resistor DC bus  Tip! Now mount the barrier between mains input and power terminals, if had been removed to have more free space for wiring. Mains  4.6-27 EDS94SPP101 EN 3.1-04/2007 Terminal X105 Labelling Description Rb1 Rb2 Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] 95 000 14 124 Terminal X100 Labelling Description +UG -UG Alternative option for DC-bus voltage connection (compatible to 9300 series). Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] Device size 8S:

Flexible With wire end ferrule 95 000 14 124 Inbus 5 Terminal X100 Marking Description SSP94KL0X8 L1 L2 L3 Connection of the mains phases L1, L2, L3  Connection for the PE conductor on the supply side with M8 ring cable lug Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] Device size 8S: Flexible With wire end ferrule 95 000 14 124 Inbus 5 M8 ring cable lug 95 000 9.5 84 WAF 13