Lenze — 6.3.3 Operation at rated mains voltage 500 V

6 6.3 6.3.3 DC power supply modules Rated data (devices for 400/500V mains) Operation at rated mains voltage 500 V Internal brake chopper data I BRmax , P BRmax Periodic load change of 0.5 s and recovery time of 4.5 s R Bmin Nominal value, ±10 % Permanent current, r.m.s. R.m.s. value - important for cable dimensioning  6.3-10 EDS94SPP101 EN 3.1-04/2007 Switching threshold (adjustable) Minimum brake resistor Peak current Peak braking power Continuous current RMS Continuous braking power Type UBRmax [V] RBmin [Ω] IBRmax [A] PBRmax [kW] IBRd [A] PBd [kW] 790 27.0 29.3 23.1 10.6 790 12.0 65.8 52.0 29.4 790 5.0 158 125 63.5 790 2.8 282 223 113