Lenze — 7.4.3 DC-power requirements

DC-bus operation Rated data DC-power requirements 7 7.4 7.4.3 7.4.3 DC-power requirements Use the below table to determine the power requirements of the devices used in the DC busfor therated mainsvoltage U Lr and thedevice-dependent power loss. Multi Drives Single Drives Tab.

7.4-5  7.4-5 EDS94SPP101 EN 3.1-04/2007 Power requirements Par [W] with rated current Power loss Type ULr = 230 V ULr = 400 V ULr = 500 V PV [W] E94AMxE0024 500 900 1000 100 E94AMxE0034 900 1600 1700 120 E94AMxE0044 1400 2500 2700 150 E94AMxE0074 2500 4400 4800 190 E94AMxE0094 3300 5800 6400 230 E94AMxE0134 4700 8100 8900 280 E94AMxE0174 5900 10300 11200 320 E94AMxE0244 8400 14700 16100 420 E94ASxE0024 500 900 1000 110 E94ASxE0034 900 1600 1700 130 E94ASxE0044 1400 2500 2700 160 E94ASxE0074 2500 4400 4800 210 E94ASxE0134 4700 8100 8900 320 E94ASxE0174 5900 10300 11200 380 E94ASxE0244 8400 14700 16100 500 E94ASxE0324 11500 20000 21800 750 E94ASxE0474 16900 29300 32000 1050 E94ASxE0594 19000 33100 40200 1100 E94ASxE0864 30800 53600 58700 1500 E94ASxE1044 37300 64800 70900 1800 E94ASxE1454 - 90000 113000 2100 E94ASxE1724 - 107000 134000 2200 E94ASxE2024 - 126000 157000 2600 E94ASxE2454 - 153000 191000 3300 E94ASxE2924 - 182000 228000 4100 E94ASxE3664 - 228000 285000 4900 E94ASxE4604 - 287000 359000 9200 E94ASxE5724 - 357000 446000 11300 E94ASxE6354 - 396000 495000 12500 E94ASxE6954 - 433000 542000 14700