User Manual of A90 Series Inverter terminal will not output the active level. description of the function code F03.08. This function code is subject to bit operation. For specific settings, refer to the Function i output Valid Invalid Level output Valid Invalid Valid delay Invalid delay Single pulse output Valid Invalid Pulse output width Fig. 7-15 Schematic Diagram of Level and Single Pulse Output of Digital Output Terminal When the status of the selected function changes, the corresponding output terminal will make a response with delay based on the function code settings. At present, the terminals Y1 and R1 support this function. Details under default conditions:
When the function changes from the invalid to valid status and is maintained with the valid delay, the corresponding output terminal will output the active level. When the function changes from the valid to invalid status and is maintained with the invalid delay, the corresponding output terminal will output the inactive level. ★ If the function code is set to 0.000s, the delay will be invalid.
157 Function Default Function code name Parameter description Unit Attribute code setting F03.09 Y1 valid delay time 0.000-30.000 s 0.000 ● F03.10 Y1 invalid delay time 0.000-30.000 s 0.000 ● F03.13 R1 valid delay time 0.000-30.000 s 0.000 ● F03.14 R1 invalid delay time 0.000-30.000 s 0.000 ● Function Parameter Default Function code name Unit Attribute code description setting F03.17 Single pulse time of 0.001 - 30.000 s 0.250 ●