User Manual of A90 Series Inverter F13.01=1:AI1 F13.01=2:AI2 The torque is dependent on AI (percentage) * F13.02. F13.01=6: communication setting The torque depends on the communication and the like.  If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific setting percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%, as detailed in Table 0-2.

For the general communication (F10.05=0), the specific setting percentage is “7003H (torque communication setting) * F13.02 (digital torque setting)”, and the 7003H data range is -200.00% to 200.00%, as detailed in Table 0-2. For diversified torque applications, the A90 series inverter supports the multi-segment torque function. Specifically, the input terminal functions “17: multi-segment torque terminal 1” and “18: multi-segment torque terminal 2” need to be set. See the instruction Table 7-19 for details.

Table 7-19 Combination of Multi-segment Torque Command and Multi-segment Torque Terminal 225 Function Function code Default Parameter description Unit Attribute code name setting F13.03 Multi-segment torque 1 -200.0 - 200.0 % 0.0 ● F13.04 Multi-segment torque 2 -200.0 - 200.0 % 0.0 ● F13.05 Multi-segment torque 3 -200.0 - 200.0 % 0.0 ● 18: multi-segment 17: multi-segment torque Number of Torque setting torque terminal 2 terminal 1 Segments Invalid Invalid Multi-segment torque 1 Depending on the F13.01 setting Invalid Valid Multi-segment torque 2 F13.03 Valid Invalid Multi-segment torque 3 F13.04