NC Error Codes Diagnostics 93 Version: 1.0 Error(Hex) Error(Dec) Error Type Description Value range: [0, 1] Unit: 1 4414 17428 Parameter "Minimum clearance between activation of the hardware latch and appearance of the sync pulse" (NOT IMPLEMENTED) The value for the minimum clearance in increments between activation of the hardware latch and occurrence of the sync/zero pulse ("latch valid") during a referencing procedure is not allowed. Value range: [0, 65536] Unit: INC 4415 17429 Parameter "External sync pulse" (NOT IMPLEMENTED) The value of the activation or deactivation of the external sync pulse in a referencing procedure is not allowed. Value 0: Passive Value 1: Active Value range:
[0, 1] Unit: 1 4416 17430 Parameter "Scaling of the noise rate is not allowed" The value of the scaling (weighting) of the synthetic noise rate is not allowed. This parameter exists only in the simulation encoder and serves to produce a realistic simulation. Value range: [0, 1000000] Unit: 1 4417 17431 Parameter „Tolerance window for modulo-start“ The value for the tolerance window for the modulo-axis-start is invalid. The value must be greater or equal than zero and smaller than the half encoder modulo-period (e. g. in the interval [0.0,180.0) ). Value range: [0.0, 180], Max: 0.5*modulo-periode Unit: e. g.
mm or degree 4418 17432 Parameter „Encoder reference mode“ The value for the encoder reference mode is not allowed, resp. is not supported for this encoder type. Value range: [0, 5] Unit: 1 4419 17433 Parameter „Encoder evaluation direction“ The value for the encoder evaluation direction (log. counter direction) is not allowed. Value range: [0, 3] Unit: 1 441A 17434 Parameter „Encoder reference system“ The value for the encoder reference system is invalid (0: incremental, 1: absolute, 2: absolute+modulo). Value range: [0, 2] Unit: 1 441B 17435 Parameter „Encoder position initialization mode“ When starting the TC system the value for the encoder position initialization mode is invalid.
Value range: [0, 1] Unit: 1 441C 17436 Parameter „Encoder sign interpretation (UNSIGNED- / SIGNED- data type)“ The value for the encoder sign interpretation (data type) for the encoder the actual increment calculation (0: Default/not defined, 1: UNSIGNED, 2:/ SIGNED) is invalid. Value range: [0, 2] Unit: 1 441D 17437 Parameter “Homing Sensor Source” The value for the encoder homing sensor source is not allowed, resp. is not supported for this encoder type. Value range: [0, 16] Unit: 1 4420 17440 Parameter "Software end location monitoring minimum not allowed" The value for the activation of the software location monitoring minimum is not allowed. Value range: [0, 1] Unit:
1 4421 17441 Parameter "Software end location monitoring maximum not allowed" The value for the activation of the software location monitoring maximum is not allowed.